User Manual

78 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
Main menu > Commissioning > RF connections
> RF repeater > Other RF devices > Connect device:
Confirm subentry “Connect device“ by pressing the Menu/ok button. To make
the connection, you are prompted to press the binding button on the device to
be connected.
Connecting RF adapter plugs KRF960 and KRF961
Press the button on the RF adapter plug. The LED lights up permanently.
When it starts blinking, you can release the button.
A successful connection appears on the display of the central apartment unit
and confirmed with a beep.
Connecting GAMMA wave actuators
Now, press the button on the respective GAMMA wave devices for at least 10
seconds. To confirm a successful connection, the central apartment unit deliv-
ers a beep.
For detailed information on commissioning the GAMMA wave compo-
nents, refer to the documentation covering the GAMMA wave prod-
ucts.
Testing radio connections
The radio connections between the central apartment unit and the following
devices can be tested at any time:
Room temperature sensors
Room units
Radiator control actuators
Heating circuit controllers
Multi-controllers
RF repeaters
Meteo sensors
Press briefly the binding or the multifunction button on the device. If the con-
nection works, the central apartment unit delivers 3 successive beeps. If the
central apartment unit is on the default picture or on one of the info pages, an
additional window with the respective device information appears. The window
can be hidden again by pressing the Menu/ok or the Esc button.