User Manual
75 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
Connect the window / door state output
Inform the central apartment unit that you want to use a universal relay output
Qx of a heating circuit controller or a multi-controller as a window / door state
output:
Main menu > Commissioning > RF connections
> Outputs > Window /door state > Connect device:
Confirm subentry “Connect device“ by pressing the Menu/ok button. To make
the connection, you are prompted to press the binding button on the device to
be connected.
Use the channel selection button (CH) to select a universal relay output Qx of
the heating circuit controller or multi-controller. The LED of the selected chan-
nel blinks. If the selected channel is not yet connected, the binding LED
flashes.
Now, press the binding button on the heating circuit controller or multi-
controller. The LED lights up green. When it starts blinking, you can release
the binding button.
A successful connection appears on the display of the central apartment unit
and is confirmed with a beep. Close the binding process by pressing the
Menu/ok button.
Connect the output for exhaust hood
Inform the central apartment unit that you want to use a universal relay output
Qx of a heating circuit controller or multi-controller as a exhaust hood output:
Main menu > Commissioning > RF connections
> Outputs > Exhaust hood > Connect device:
Confirm subentry “Connect device“ by pressing the Menu/ok button. To make
the connection, you are prompted to press the binding button on the device to
be connected.
Use the channel selection button (CH) to select a universal relay output Qx of
the heating circuit controller or multi-controller. The LED of the selected chan-
nel blinks. If the selected channel is not yet connected, the binding LED
flashes.
Now, press the binding button on the heating circuit controller or multi-
controller. The LED lights up green. When it starts blinking, you can release
the binding button.
A successful connection appears on the display of the central apartment unit
and is confirmed with a beep. Close the binding process by pressing the
Menu/ok button.