User Manual

72 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
Connect input for absence
Inform the central apartment unit that you want to use a universal input B of a
heating circuit controller or a universal input Xx of a multi-controller for con-
necting an absence contact:
Main menu > Commissioning > RF connections
> Inputs > Absence > Connect device:
Confirm subentry “Connect device“ by pressing the Menu/ok button. To make
the connection, you are prompted to press the binding button on the device to
be connected.
Use the channel selection button (CH) to select universal input B of the heat-
ing circuit controller or a universal input Xx of the multi-controller. The LED of
the selected channel blinks. If the selected channel is not yet connected, the
binding LED flashes.
Now, press the binding button on the heating circuit controller or multi-
controller. The LED lights up green. When it starts blinking, you can release
the binding button.
A successful connection appears on the display of the central apartment unit
and is confirmed with a beep. Close the binding process by pressing the
Menu/ok button.
Connect the input for twilight
Inform the central apartment unit that you want to use a universal input B of a
heating circuit controller or a universal input Xx of a multi-controller or a door /
window contact wave AP 260 for connecting a twilight switch:
Main menu > Commissioning > RF connections
> Inputs > Twilight > Connect device:
Confirm subentry “Connect device“ by pressing the Menu/ok button. To make
the connection, you are prompted to press the binding button on the device to
be connected.
If you want to use a universal input B of a heating circuit controller or a univer-
sal input Xx of a multi-controller as a twilight input, select it with the channel
selection button (CH) and press the binding button. The LED lights up green.
When it starts blinking, you can release the binding button.
If you want to use the external input of a door / window contact wave AP 260
as a twilight input, press the button on the door / window contact for about 1
second. Then, the LED blinks for a few seconds.
A successful connection appears on the display of the central apartment unit
and is confirmed with a beep. Close the binding process by pressing the
Menu/ok button.