Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
Confirm subentry “Connect device“ by pressing the Menu/ok button. To make
the connection, you are prompted to press the binding button on the device to
be connected.
Select a universal relay output Qx with the channel selection button (CH) on
the heating circuit controller or multi-controller. The LED of the selected chan-
nel blinks. If the selected channel is not yet connected, the binding LED flashes.
Now, press the multifunction button on the heating circuit controller or multi-
controller. The LED lights up green. When it starts blinking, you can release
the binding button.
A successful connection appears on the display of the central apartment unit
and is confirmed with a beep. Close the binding process by pressing the
Menu/ok button.
Connect the output for the electric immersion heater
Inform the central apartment unit that you want to use a universal relay output
Qx of a heating circuit controller for connecting the electric immersion heater:
Main menu > Commissioning > RF connections > DHW
> Electric immersion heater > Connect device:
Confirm subentry “Connect device“ by pressing the Menu/ok button. To make
the connection, you are prompted to press the binding button on the device to
be connected.
Select a universal relay output Qx with the channel selection button (CH) on
the heating circuit controller or multi-controller. The LED of the selected chan-
nel blinks. If the selected channel is not yet connected, the binding LED
flashes.
Now, press the binding button on the heating circuit controller or multi-
controller. The LED lights up green. When it starts blinking, you can release
the binding button.
A successful connection appears on the display of the central apartment unit
and is confirmed with a beep. Close the binding process by pressing the
Menu/ok button.
Connect meteo sensor
Inform the central apartment unit that you want to assign a meteo sensor:
Main menu > Commissioning > RF connections
> Meteo sensor > Connect device:
The QAC910 meteo sensor is automatically switched on as soon as the bat-
teries are inserted.
When switching on (power-up), the batteries’ capacity is tested. If the capacity
is sufficient, the green LED is lit for 2 seconds during the test.
If the batteries’ capacity is not sufficient for operation, the LED is lit red
for 2 seconds – provided capacity is still sufficient.