User Manual
65 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
Now, press the binding button on the multi-controller. The LED lights up
green. When it starts blinking, you can release the binding button.
A successful connection appears on the display of the central apartment unit
and confirmed with a beep. Close the binding process by pressing the
Menu/ok button.
Connect DHW components
The following DHW plant components are assigned appropriate inputs or
outputs:
• DHW sensor
• DHW pump / valve
• Electric immersion heater
On the DHW plant components, the respective input and output
functions must be set to “Via RF“, enabling an input or output of a
heating circuit controller / multi-controller to be assigned to them.
Connect the input for the DHW sensor
Inform the central apartment unit that you want to use a universal input B of a
heating circuit controller or a universal input Xx of a multi-controller as a DHW
sensor input:
Main menu > Commissioning > RF connections
> DHW > DHW sensor > Connect device:
Confirm subentry “Connect device“ by pressing the Menu/ok button. To make
the connection, you are prompted to press the binding button on the device to
be connected.
Select universal input B on the heating circuit controller or a universal input Xx
on the multi-controller with the channel selection button (CH). The LED of the
selected channel blinks. If the selected channel is not yet connected, the
binding LED flashes.
Now, press the binding button on the heating circuit controller or multi-
controller. The LED lights up green. When it starts blinking, you can release
the binding button.
A successful connection appears on the display of the central apartment unit
and is confirmed with a beep. Close the binding process by pressing the
Menu/ok button.
Connect the output for the DHW pump / valve
Inform the central apartment unit that you want to use a universal relay output
Qx of a heating circuit controller or multi-controller for connecting the DHW
pump / valve:
Main menu > Commissioning > RF connections
> DHW > DHW pump/valve > Connect device: