User Manual
61 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
Now, press the binding button on the multi-controller. The LED lights up
green. When it starts blinking, you can release the binding button.
A successful connection appears on the display of the central apartment unit
and confirmed with a beep. Close the binding process by pressing the
Menu/ok button.
Connect input for flow sensor / return sensor
Inform the central apartment unit that you want to use a universal input Xx of a
multi-controller as a flow or return temperature sensor input:
Main menu > Commissioning > RF connections > Room groups
> Room group X > Flow temperature sensor > Connect device:
Main menu > Commissioning > RF connections > Room groups
> Room group X > Return temperature sensor > Connect device:
Confirm subentry “Connect device“ by pressing the Menu/ok button. To make
the connection, you are then prompted to press the binding button on the
multi-controller.
Use the channel selection button (CH) on the multi-controller to select the
required universal input Xx. The LED of the selected channel blinks. If the
selected channel is not yet connected, the binding LED starts flashing.
Now, press the binding button on the multi-controller. The LED lights up
green. When it starts blinking, you can release the binding button.
A successful connection appears on the display of the central apartment unit
and confirmed with a beep. Close the binding process by pressing the
Menu/ok button.
Connect output for room group pump
Inform the central apartment unit that you want to use a universal relay output
Qx of the heating circuit controller or multi-controller for connecting the room
group pump:
Main menu > Commissioning > RF connections > Room groups
> Room group X > Room group pump > Connect device:
Confirm subentry “Connect device“ by pressing the Menu/ok button. To make
the connection, you are then prompted to press the binding button on the
device to be connected.
Use the channel selection button (CH) on the heating circuit controller or multi-
controller to select a universal relay output Qx. The LED of the selected chan-
nel blinks. If the selected channel is not yet connected, the binding LED starts
flashing.
Now, press the binding button on the heating circuit controller or multi-controller.
The LED lights up green. When it starts blinking, you can release the binding
button.