User Manual

56 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
If, thus far, none of the heating controller channels has been connected, the
binding LED flashes. The other LEDs remain dark.
When you press the multifunction button, the status of the individual
channels is indicated. The LEDs of the channels already connected
light up, those of the channels not connected remain dark. When
releasing the button, the heating circuit controllers return to normal
operation after 10 seconds. When a channel is selected, the binding
LED indicates the status of the respective channel.
Example: Heating circuit controller RRV912
LED = light emitting diode
F = multifunction button
CH = channel selection button
The connection of the heating circuit controller is made individually for each
required channel.
To connect a heating circuit controller channel, press the channel selection
button (CH) to select a suitable channel (channels Y1 and Y2 with the
RRV912, channels 1..8 with the RRV918). The LED of the selected channel
blinks. If the selected channel is not yet connected, the binding LED flashes.
If no button is pressed for 10 minutes, the heating circuit controller
returns to normal operation.
Now, press the multifunction button on the heating circuit controller. The LED
lights up green. As soon as it starts blinking, you can release the multifunction
button.
The first channel of a room that has been connected assumes lead
control. The other channels of the same room that have been con-
nected is controlled in parallel.
After successful connection, the heating circuit controller is restarted.
Now, the heating circuit controller has returned to channel selection mode and
is ready for connecting another channel.
Connect window contacts
The window / door contact wave AP260 is ready to operate as soon as the
inserted batteries supply power.
LED
F
CH