Indoor air quality sensor
An indoor air quality sensor facilitates control of the ventilation plant based on
the adjusted indoor air quality setpoints.
State whether an indoor air quality sensor is installed and from where the
central apartment unit receives the measured value
--- Inactive – no indoor air quality sensor installed
Via RF / S-Mode Humidity sensor (DC 0..10 V) connected to univer-
sal input Xx of an RRV934 multi-controller
Indoor air quality sensor signal received through S-
Mode object via KNX TP1 *
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode
devices on KNX TP1 is made with the help of a commissioning tool (ETS).
Main menu > Commissioning > Extra configuration
> Ventilation > Inputs > IAQ sensor:
Factory setting ---
Your setting ---
Via RF / S-Mode
Open fireplace mode
In apartments using controlled room ventilation, the external ventilation
equipment must often be switched to a special operating mode (open fireplace
mode) when the open fireplace is used, thus preventing underpressure and,
therefore, the risk of harmful emissions.
Open fireplace mode of the ventilation equipment can be displayed on the
central apartment unit by closing the respective input.
State whether a contact for open fireplace mode is installed and from where
the central apartment unit receives its state.
--- Inactive – no fireplace mode contact installed
Via RF / S-Mode Fireplace mode contact connected to universal
input B of an RRV91... heating circuit controller or
to universal input Xx of an RRV934 multi-controller
Fireplace mode signal received through S-Mode
object via KNX TP1 *
B (local) Fireplace mode contact connected to universal input
B of the central apartment unit
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode
devices on KNX TP1 is made with the help of a commissioning tool (ETS).
Main menu > Commissioning > Extra configuration
> Ventilation > Inputs > Fireplace mode:
Factory setting ---
Your setting ---
Via RF / S-Mode
B (local)