Main menu > Commissioning > Basic configuration
> Outputs > Window/door state:
Factory setting ---
Your setting ---
Via RF / S-Mode
Q1 (local)
Exhaust hood
To release the exhaust hood, at least one of the windows in the selected
rooms must be open, thus making certain that operation of the exhaust hood
does not produce underpressure in the room.
State whether a relay should be used to release the exhaust hood and how it
is controlled.
--- Inactive – release of exhaust hood not required
Via RF / S-Mode Release of exhaust hood via:
Relay output Qx of an RRV91… heating circuit
controller or RRV934 multi-controller
S-Mode object on KNX TP1 *
Q1 (local) Use relay output Q1 of the central apartment unit for
release of the exhaust hood
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode
devices on KNX TP1 is made with the help of a commissioning tool (ETS).
Main menu > Commissioning > Basic configuration
> Outputs > Exhaust hood:
Factory setting ---
Your setting ---
Via RF / S-Mode
Q1 (local)
Configure RF repeaters
Activate the required number of RF repeaters. For that, select every RF re-
peater required (1…3) and change the setting from “---“ to ”Active“.
Main menu > Commissioning > Basic configuration
> RF repeater > Repeater X:
Repeater 1 Repeater 2 Repeater 3
Factory setting --- --- ---
Your setting ---
Active
---
Active
---
Active