User Manual
44 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
Status output
When the appropriate output terminal closes, the central apartment unit indi-
cates the occurrence of events via an external component (e.g. signal lamp or
horn).
The events (smoke, window/door supervision, fault inputs 1 - 8) leading to
closure of the status output can be defined via parameter “Events status out-
put“. For a description of this parameter, refer to the Operating Instructions,
section “Supervision“.
State whether a status output is used and how it is controlled.
--- Inactive – status output not required
Via RF / S-Mode Deliver state of status output via:
• Relay output Qx of an RRV91… heating
circuit controller or RRV934 multi-controller
• S-Mode object on KNX TP1 *
Q1 (local) Relay output Q1 of the central apartment unit
used as a signal output
* The connection of the relevant S-Mode objects of the central apartment unit to the relevant S-Mode
devices on KNX TP1 is made with a commissioning tool (ETS)
Main menu > Commissioning > Basic configuration
> Outputs > Status output:
Factory setting ---
Your setting ---
Via RF / S-Mode
Q1 (local)
Window / door state output
If at least one window / door is open, the respective output terminal is closed.
As a result, an open window / door can be shown via an additional external
component.
State whether a window / door state output is used and how it is controlled.
--- Inactive – window / door state output not
required
Via RF / S-Mode Window / door state delivered via:
• Relay output Qx of an RRV91… heating
circuit controller or RRV934 multi-controller
• S-Mode object on KNX TP1 *
Q1 (local) Relay output Q1 of the central apartment unit
used as a window / door state output
* The connection of the relevant S-Mode objects of the central apartment unit to the relevant S-Mode
devices on KNX TP1 is made with a commissioning tool (ETS)