User Manual
42 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
--- Inactive – twilight switch not installed
Via RF / S-Mode • Twilight switch connected to universal input B
of an RRV91… heating circuit controller or to
universal input Xx of an RRV934 multi-controlller
• Twilight switch connected to external contact
input of a door / window contact wave AP 260
• Twilight signal of an S-Mode object is received
via KNX TP1 *
B (local) Twilight switch connected to universal input B of
the central apartment unit
* The connection of the relevant S-Mode objects of the central apartment unit to the relevant S-Mode
devices on KNX TP1 is made with a commissioning tool (ETS)
Main menu > Commissioning > Basic configuration > Inputs > Twilight:
Factory setting ---
Your setting ---
Via RF / S-Mode
B (local)
Configure outputs
Outputs can be used to transmit signals to external components.
Activate the required output function by defining how the central apartment
unit delivers the signal (Via RF, Q1 (local)).
Heat demand relay
When the appropriately defined output terminal closes, a heat demand signal
is transmitted to the heat source.
State whether a heat demand relay is used and how it is controlled.
--- Inactive – heat demand relay not required
Via RF Relay output Qx of an RRV91… heating
circuit controller or RRV934 multi-controller
used as a heat demand relay
Q1 (local) Relay output Q1 of the central apartment
unit used as a heat demand relay
Main menu > Commissioning > Basic configuration
> Outputs > Heat demand relay:
Factory setting ---
Your setting ---
Via RF
Q1 (local)