User Manual

41 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
Absence
“Absence“ is triggered when the respective input terminal closes.
The room temperature setpoints are switched to the respective absence set-
point (per room) and any activated time program for presence simulation
starts via the switching groups.
DHW heating, ventilation and cooling also operate according to the operating
mode selected for the period of absence.
For a detailed description of ”Absence“, refer to the Operating Instructions.
State whether an external absence contact is used and from where the central
apartment unit receives its status.
--- Inactive – absence contact not installed
Via RF / S-Mode Absence contact connected to universal input
B of an RRV91… heating circuit controller or
to universal input Xx of an RRV934 multicon-
troller
Absence signal of an S-Mode object is re-
ceived via KNX TP1 *
B (local) Absence contact connected to universal input B
of the central apartment unit
* The connection of the relevant S-Mode objects of the central apartment unit to the relevant S-Mode
devices on KNX TP1 is made with a commissioning tool (ETS)
Main menu > Commissioning > Basic configuration > Inputs > Absence:
Factory setting ---
Your setting ---
Via RF / S-Mode
B (local)
Twilight
When the respective input terminal closes (e.g. initiated by a twilight switch),
the twilight state changes from Bright to Dark, impacting the switching groups
in accordance with the settings made (e.g. for lighting and blinds control).
For a description of the settings required for the switching group
responses, refer to the Operating Instructions, section “Triggering
switching groups via an event“.
State whether an external twilight switch is used and from where the central
apartment unit receives its status.