User Manual
34 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Commissioning the system 23.08.2008
The central apartment unit transmits the switching group commands to the
switching group actuators – via RF and the wired bus. The output signal can
be forwarded to the following types of devices:
Switching group function Supported types of actuators / suppliers
Switch, Dim
Switch and dim actuators:
• RF adapter plugs KRF96…
• Siemens: GAMMA wave
• Hager: tebis radio
• Any brand: S-Mode KNX TP1 *
Blind
Blind actuators:
• Siemens: GAMMA wave
• Hager: tebis radio
• Any brand: S-Mode KNX TP1 *
Scene
Scene-compatible switch and dim
actuators:
• RF adapter plugs KRF96…
• Siemens: GAMMA wave
• Hager: tebis radio
• Any brand: S-Mode KNX TP1 *
* The connection of the relevant S-Mode objects of the central apartment unit to the relevant S-Mode
devices on KNX TP1 is made with a commissioning tool (ETS)
Switching group relays
Switching groups with selected “Switch“ function can be assigned a relay
output.
State whether a switching group relay is used and how it is controlled.
--- Inactive – no switching group relay required
Via RF Relay output Qx of an RRV91… heating circuit control-
ler or RRV934 multi-controller used as a switching
group relay
Q1 (local) Relay output Q1 of the central apartment unit used as a
switching group relay
Main menu > Commissioning > Basic configuration > Switching groups
> Switching group X > Relay output:
Switching
group
Factory setting Your setting
1 --- --- (none)
Via RF
Q1 (local)
2 --- --- (none)
Via RF
Q1 (local)
3 --- --- (none)
Via RF
Q1 (local)