Building Technologies Commissioning the system 23.08.2008
DHW temperature sensor
State whether a DHW temperature sensor is used and from where the central
apartment unit receives the actual value.
--- Inactive – no DHW sensor installed
Via RF DHW sensor connected to universal input B of an
RRV91… heating circuit controller or universal input
Xx of an RRV934 multi-controller
B (local) DHW sensor connected to universal input B of the
central apartment unit
Main menu > Commissioning > Basic configuration
> DHW > DHW sensor:
Factory setting ---
Your setting ---
Via RF
B (local)
DHW charging pump / diverting valve
State whether a DHW charging pump or DHW diverting valve is used and how
it is controlled.
--- Inactive – no DHW charging pump / diverting valve
installed
Via RF DHW charging pump / diverting valve connected to
relay output Qx of an RRV91… heating circuit con-
troller or RRV934 multi-controller
Q1 (local) DHW charging pump / diverting valve connected to
relay output Q1 of the central apartment unit
Main menu > Commissioning > Basic configuration
> DHW > DHW pump/valve:
Factory setting ---
Your setting ---
Via RF
Q1 (local)