Building Technologies Commissioning the system 23.08.2008
Configure DHW charging
2707Z30
If you want DHW charging controlled
directly by the central apartment unit,
activate the required DHW plant com-
ponents (DHW sensor, pump / valve,
electric immersion heater).
If you require external DHW heating
controlled remotely via KNX TP1,
activate ”Operation external DHW“.
If there is a request for DHW, the room group pumps are not put into
operation. For this reason – from the hydraulics point of view – DHW
must always be installed upstream of the room groups.
The type of DHW heating depends on the installed DHW components accord-
ing to the following table:
DHW
sensor
DHW pump/
valve
Electric
immersion
heater
Resulting type of DHW heating
--- --- --- Inactive: No local DHW heating
available
Installed Installed --- Controlled storage tank charging
with DHW pump / valve only
Installed Installed Installed Controlled alternating storage tank
charging: DHW pump / valve in the
winter, electric immersion heater in
the summer
Installed --- Installed Controlled storage tank charging
with electric immersion heater only
--- --- Installed Uncontrolled storage tank charging
with electric immersion heater only.
The DHW setpoint must be set on
the electric immersion heater
--- Installed --- Configuration error: DHW sensor
missing
Installed --- --- Configuration makes no sense; no
storage tank charging possible
External DHW heating can be operated remotely only if there is no
local DHW heating.