User Manual

104 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Function settings 23.08.2008
Main menu > DHW > Legionella function > Legionella setpoint:
Guide value 70 °C
Your setting
Legionella protection frequency
Decide and set how often the legionella function should be activated. It can be
performed daily or weekly. With the weekly legionella function, the weekday
can be selected (Mo..Su).
When using setting “Never“, the legionella function is always deacti-
vated.
Main menu > DHW > Legionella function > Legio prot freq:
Guide value Monday
Your setting Never
Daily
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Legionella protection time
Define the time of day (00:00..24:00) the legionella function should be started.
Main menu > DHW > Legionella function > Legio prot time:
Factory setting 05:00
Your setting
Legionella protection period
When the legionella function is active, the DHW storage tank is maintained at
the legionella protection setpoint for the period of time set here (0.00 – 6.00
hours).
Main menu > DHW > Legionella function > Legio prot period:
Guide value 00.30 h.min
Your setting