User Manual

103 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Function settings 23.08.2008
Startup delay
The startup delay (00.00..60.00 mm.ss) prevents the individual ventilation
stages from switching on too quickly. Each time a stage is switched on, the
delay time must elapse before the next stage can be switched on.
Main menu > Ventilation > Ventilation settings > Startup delay:
Factory setting 00.00 mm.ss
Your setting
Locking time
After switching off, each ventilation stage remains locked for the period of time
set here (00.00..60.00 mm.ss). It can be switched on again only when this
time has elapsed.
The locking time is the same for all stages.
Main menu > Ventilation > Ventilation settings > Locking time:
Factory setting 00.00 mm.ss
Your setting
Rundown time
As soon as a ventilation stage is switched off, the “Rundown time“
(00.00..60.00 mm.ss) starts. The next lower stage is switched on only when
this time has elapsed.
Main menu > Ventilation > Ventilation settings > Rundown time:
Guide value 00.00 mm.ss
Your setting
DHW
Frost protection setpoint
Set the DHW setpoint to be used in Protection mode.
Main menu > DHW > Setpoints > Frost prot setp:
Guide value 5 °C
Your setting
Legionella setpoint
Set the setpoint the DHW storage tank should maintain during the time the
legionella function is performed.