User Manual

102 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Function settings 23.08.2008
Minimum operating time night cooling
If all switch-on conditions for night cooling are met, it is switched on for at least
the period of time set here (0..720 min).
Main menu > Ventilation > Night cooling > Operating time min:
Factory setting 30 min
Your setting
Reference room night cooling
To be able to determine the necessary temperature differential, the central
apartment unit requires the room temperature plus the outside temperature.
By selecting the reference room, you tell the controller which of the room
sensors is the most suited for acquiring the reference value.
Main menu > Ventilation > Night cooling > Reference room:
Factory setting Room 1
Your setting Room 1, Room 2, Room 3, Room 4,
Room 5, Room 6, Room 7, Room 8,
Room 9, Room 10, Room 11, Room 12
Outside temperature limit value night cooling
This setting defines the lowest outside temperature (0..50 °C) at which night
cooling is permitted. Below this temperature level, night cooling is locked.
Main menu > Ventilation > Night cooling > OT limit:
Factory setting 12 °C
Your setting
Room - outside temperature delta night cooling
Set here the by how much as a minimum the outside temperature must lie
below the room temperature (0..20 K) for night cooling to be switched on.
Main menu > Ventilation > Night cooling > Room-outs delta:
Factory setting 5 K
Your setting