User Manual
101 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Function settings 23.08.2008
Switching differential of humidity limitation
If the ventilation system was switched on because humidity in the room was
too high, it is switched off again when humidity drops below the “Humidity limit
value“ by the switching differential set here (1..20%).
Main menu > Ventilation > Humidity limitation > Switching diff:
Factory setting 5%
Your setting
Running time humidity limitation
The humidity limitation interval starts with the running time set here (0..720 min).
During this period of time, the ventilation system operates at the preselected
stage.
Main menu > Ventilation > Humidity limitation > Running time:
Factory setting 30 min
Your setting
Pause time humidity limitation
When the “Running time“ has elapsed, the ventilation system is switched off
for the pause time set here (0..720 min) before it resumes operation.
Main menu > Ventilation > Humidity limitation > Pause time:
Factory setting 60 min
Your setting
Air humidity at 0 V / 10 V
To limit humidity, a humidity sensor (DC 0..10 V) must be connected.
The humidity sensor must be located in the room itself, thus ensuring
that air also circulates around the sensor when the ventilation system
is off. Do not install the sensor in the extract air duct.
The humidity value for 0 V and 10 V (0..100% r.h.) can be set here.
Main menu > Ventilation > Humidity limitation > Humidity 0 V:
Factory setting 0% r.h.
Your setting
Main menu > Ventilation > Humidity limitation > Humidity 10 V:
Factory setting 100% r.h.
Your setting