User Manual
10 / 124
Siemens Synco™ living CE1C2707en
Building Technologies Mounting and installation 23.08.2008
Mounting and installation
Mount the central apartment unit
Mounting regulations
• The central apartment unit is designed in compliance with safety class II
and must be mounted accordingly.
• Power may be applied to the unit only when completely mounted. Other-
wise, there is a risk of electric shock by the connection terminals.
• The unit must not be exposed to dripping water.
• The permissible environmental conditions specified in the technical data
must be observed (refer to Data Sheet N2707en).
• Sufficient space must be provided for fitting / removing the unit cover and
for connecting the service tool (> 70 mm below and > 10 mm above the
unit).
Mounting location
The central apartment unit consists of electronics section and base.
The base is designed for wall mounting (on an interior wall of the apartment).
We recommend to mount the unit in an easily accessible space (e.g. in the
living room or the lobby). For convenient operation, the recommended mount-
ing height is 1.5 m above the floor.
2707Z31
> 70 mm
> 10 mm
1.5 m
The central apartment unit communicates with most system components via
radio. To ensure optimum radio coverage, the following points should be
observed:
• The distance to devices with electromagnetic emissions, such as wireless
telephones, TV sets, PCs, microwave appliances, etc., should be at least
1 m
• Larger items made of steel or construction elements with metal meshes
(e.g. special glass or concrete), or metal foils in thermal insulation materials,
mirrors or metal-coated heat absorbing glass, can have an impact on the
range