User Manual

50 / 110
Siemens Synco™ living CE1B2740en
Building Technologies Central apartment unit QAX9x3 13.12.2010
Operating mode for absence
The desired ventilation operating mode for absence (see page 31) is set via
the following operating line.
Main menu > Ventilation > Operating mode > Optg mode absence:
--- Absence has no influence on the ventilation mode.
(factory setting)
Comfort
Ventilation runs on Comfort stage setpoint during absence.
Precomfort
Ventilation runs on Precomfort stage setpoint during ab-
sence.
Economy
Ventilation runs on Economy stage setpoint during ab-
sence.
Protection
Ventilation runs on Protection stage setpoint during ab-
sence.
Changeover of the ventilation operating mode occurs only if the venti-
lation operating mode for absence is below that for normal operation.
The setting for the ventilation mode for absence does not depend on
the setting for room operating mode for absence. However, both op-
erating modes can be changed over via the absence button.
Stage setpoints
Stage assignment to operating modes
The individual ventilation operating modes can be assigned to the correspond-
ing ventilation stages via stage setpoints.
This setting has no influence, if ventilation is controlled by relative
humidity or air quality.
Off Ventilation off.
Stage 1 Ventilation on stage 1.
Stage 2 Ventilation on stage 2.
Stage 3 Ventilation on stage 3.
Main menu > Ventilation > Stage setpoints > Comfort:
Factory setting Stage 1
Main menu > Ventilation > Stage setpoints > Precomfort:
Factory setting Stage 1