Siemens Synco™ living CE1C2740en
Building Technologies Function settings 13.12.2010
Room controller settings
These settings are visible only if the user-defined heating type is set.
(See page 20).
P-band Xp
The room controller’s P-band can be set for every room to suit individual
needs.
Main menu > Rooms > Room X > Room controller > P-band Xp:
For your guidance, see the default settings (factory setting 2 K):
Room type Guide value Xp
Radiator heating slow 2 K
Radiator heating fast 2 K
Floor heating slow 2 K
Floor heating fast 2 K
Integral action time Tn
The room controller’s integral action time can be set for every room.
Main menu > Rooms > Room X > Room controller > Int action time Tn:
For your guidance, see the default settings (factory setting 5400 s):
Room type Guide value Tn
Radiator heating slow 5400 s
Radiator heating fast 3600 s
Floor heating slow 7200 s
Floor heating fast 5400 s