User Manual
59 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Fault input normal position
Specify the normal position for the fault inputs.
Main menu > Commissioning > Extra configuration > Faults
> Fault input X > Normal position:
Open An open contact is detected as "Not faulty"
(factory setting).
Closed A closed contact is detected as "Not faulty".
When using water detector QFP910, keep the normal position on
"Open".
Connect RF components
Notes
RF components are assigned to rooms or functions.
On the central apartment unit, configure first the required rooms (see page 20),
then activate the
required functions and set transmission mode to “Via RF“ or
”Via RF/S-mode“ (see page 25 ff.).
If you connect a device twice by mistake, the central apartment unit ig-
nores the second connection and generates an error message. There
is no beep.
After all devices are connected, check the number of channels and the
connected device types on the device list. Missing or superfluous de-
vices can also be added or removed later.
Connect RF room devices
The following RF devices can be assigned to a room:
• Room unit QAW910
• Room temperature sensor QAA910
• Radiator control actuator SSA955
• Heating circuit controller RRV91… (only heating circuit actuators)
• Door/window contacts wave AP 260
RF devices are connected room by room.
Inform the central apartment unit which room you want to assign RF room de-
vices:
Main menu > Commissioning > RF connections
> Rooms > Room X > Connect device:
Confirm entry on submenu “Connect device“ by pressing the Menu/ok button.
To connect, the system asks you to press the binding button on the device to
be connected.