User Manual
58 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Meter 4 Meter connected to the 2nd pulse input of the 1st pulse
adapter AEW2.1 of the apartment.
Meter 5 Meter connected to the 1st pulse input of the 2nd pulse
adapter AEW2.1 of the apartment.
Meter 6 Meter connected to the 2nd pulse input of the 2nd pulse
adapter AEW2.1 of the apartment.
General
meter 1
Meter connected to the 1st pulse input of the pulse adapter
AEW2.1 with plug 121.
General
meter 2
Meter connected to the 2nd pulse input of AEW2.1 with plug
121 or to the 1st pulse input of AEW2.1 with plug 124.
General
meter 3
Meter connected to the 1st pulse input of the pulse adapter
AEW2.1 with plug 122.
General
meter 4
Meter connected to the 2nd pulse input of AEW2.1 with plug
122 or to the 1st pulse input of AEW2.1 with plug 125.
General
meter 5
Meter connected to the 1st pulse input of the pulse adapter
AEW2.1 with plug 123.
General
meter 6
Meter connected to the 2nd pulse input of AEW2.1 with plug
123 or to the 1st pulse input of AEW2.1 with plug 126.
Value "Meter 1" to "Meter 6" must be set for meters allocated to bill-
ing in the apartment.
For general meters, set value "General meter 1" to "General meter 6".
In addition, a setting value can be used only for a meter.
Faults (QAX913 only)
Fault input source
Specify the source of the fault input state for central apartment unit QAX913.
Main menu > Commissioning > Extra configuration > Faults
> Fault input X > Source:
--- Inactive – fault contact not available (factory setting).
Via RF • Fault contact connected to universal input B of an
RRV91…heating circuit controller or to universal input Xx
of an RRV934 multi-controller.
• Fault contact connected to external contact input of a
door/window switch wave AP 260.
• Use water detector QFP910 as fault input.
• Fault status of an S-mode object is received via KNX TP1 *.
B (local) Fault contact connected to universal input B of the central
apartment unit.
* Connection of the respective S-mode objects of the central apartment unit to the relevant S-mode de-
vices on KNX TP1 via commissioning tool (ETS).