User Manual
38 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Supervision (QAX913 only)
Supervision contact
Closing the related input terminal (e.g. via key switch) switches over the su-
pervision state from "Inactive“ to "All monitored" or from "All monitored" to "In-
active".
Specify if an external supervision contact is used and from where the central
apartment unit receives its status.
Main menu > Commissioning > Basic configuration > Supervision
> Supervision contact:
--- Inactive – no input terminal available
(factory setting).
Via RF/S-mode • Supervision contact connected to universal input B
of an RRV91… heating circuit controller or univer-
sal input Xx of an RRV934 multi-controller.
• Supervision signal received through S-Mode ob-
ject via KNX TP1 *
B (local) Supervision contact connected to universal input B of
the central apartment unit.
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de-
vices on KNX TP1 via commissioning tool (ETS).
Supervision state
This output shows the status of supervision (e.g. on key switch). The relay
output is closed when supervision state corresponds to "Partly monitored" or
"All monitored".
Specify if a relay should be used to issue the supervision state and how it is
controlled.
Main menu > Commissioning > Basic configuration > Supervision
> Supervision state:
--- Inactive – no supervision display (factory setting).
Via RF/S-mode Supervision state issued via:
• Relay output Qx of an RRV91.. heating circuit con-
troller or RRV934 multi-controller.
• S-mode object on KNX TP1 *.
Q1 (local) Supervision state issued via relay output Q1 of the
central apartment unit.
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de-
vices on KNX TP1 via commissioning tool (ETS).