User Manual

32 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Allocation
The following allocation types are available for each meter:
Apartment The consumption values from the meter are billed to the
apartment user. (Factory setting)
General General meter whose consumption data are acquired via
this central apartment unit. Consumption data from gen-
eral meters are visible only at the expert level and are
not directly billed to the apartment user.
Source
Specify the source for the meter data for the central apartment unit:
--- Inactive – all relevant meter information and operating
lines are hidden. (Factory setting)
Pulse input
WRI9xx
Meters with pulse output are connected via a pulse input
of a consumption data interface WRI982.
M-Bus WRI9xx Meters with M-bus interface are connected via the M-bus
input of consumption data interface WRI982.
Configure heat/cooling energy meter
You can record up to 4 heat/cooling energy meters with the central apartment
unit. The meter may be a heat meter, a cooling energy meter, or a combined
heat/cooling energy meter.
An allocation type and name is assigned to each heat/cooling energy meter.
Main menu > Commissioning > Basic configuration
> Meter > Heat/cooling energy > Heat/cool X > Heat/cool X:
Main menu > Commissioning > Basic configuration
> Meter > Heat/cooling energy > Heat/cool X > Allocation:
A heat/cooling energy meter is activated as soon as the source is set to un-
equal "---".
Main menu > Commissioning > Basic configuration
> Meter > Heat/cooling energy > Heat/cool X > Source:
Enter the desired metering medium.
Main menu > Commissioning > Basic configuration
> Meter > Heat/cooling energy > Heat/cool X > Metering medium: