User Manual

30 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Factory setting
Switching group 1 - 4 Info
Switching group 5 - 8 --- (Inactive)
Prior to changing an already defined switching group function, all RF
devices connected to the switching group must be disconnected (see
page 86). Disconnect and deactivate any connected switching group
relay bef
ore switching group function "Switch" can be changed.
Per default, info pages 1 – 8 are assigned to the 4 pairs of softkeys.
Changes to info page numbers are possible at the user level. (See
operating instructions via info page direct selection).
The central apartment unit transmits the switching group commands to the
switching group actors – via RF and the wired bus. The output signal can be
forwarded to the following types of devices:
Switching group function Supported types of devices/suppliers
Switch, Dim Switching and dimming devices:
RF adapter plugs KRF96…
Siemens: GAMMA wave
Hager: tebis radio
Any brand: S-mode KNX TP1 *
Blind Blinds devices:
Siemens: GAMMA wave
Hager: tebis radio
Any brand: S-mode KNX TP1 *
Scene Scene-compatible switching and dimming de-
vices:
RF adapter plugs KRF96…
Siemens: GAMMA wave
Hager: tebis radio
Any brand: S-mode KNX TP1 *
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de-
vices on KNX TP1 via commissioning tool (ETS).
Switching group relay
Switching groups with selected “Switch“ function can be assigned a relay out-
put.
Specify if a switching group relay is used and how it is controlled.
Main menu > Commissioning > Basic configuration
> Switching groups > Switching group X > Relay output: