User Manual

22 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Commissioning the system 13.12.2010
Configure room groups
Any number of rooms can be combined to form one room group. Two inde-
pendent room groups can be formed.
The flow temperature can be controlled, a room group pump defined, and the
return temperature limited for each room group.
U1 Mixing valve for room group 1 (radiators)
U2 Mixing valve for room group 2 (floor heating)
B2/B3 Flow sensors room groups 1 and 2
M2/M3 Room group pumps 1 and 2
T Room unit or
room temperature sensor
Y1 Radiator control actuator
Y2 Heating circuit valve (2-position)
If Synco Living controls all rooms with actuators, operating states
without flow may exist in the precontroller. Use suitable hydraulic
measures (e.g. overflow or bypass) to avoid this and prevent the pre-
controller during operation to oscillate without flow.
Room group name
You can assign a name to each room group. You can also enter or change the
room group’s name after commissioning.
Main menu > Commissioning > Basic configuration
> Room groups > Room group X > Room group X:
Function
Define the function needed for the room group.
Main menu > Commissioning > Basic configuration
> Room groups > Room group X > Function: