User Manual
120 / 134
Siemens Synco™ living CE1C2740en
Building Technologies Function settings 13.12.2010
Refrigeration request 0..10 V
To be able to transmit a temperature request (for room cooling) to a refrigera-
tion request controller by means of a 0..10 V signal, the temperature setpoint
at 0 V and 10 V must be predefined for the central apartment unit. The values
in between are interpolated in a linear way.
Temperature requests above the selected temperature request threshold are
not forwarded to the heat demand controller (0 V).
Setpoint in °C at DC 0 V
Setpoint in °C at DC 10 V
Threshold value of temperature request (temperatures above this level are interpreted as “No de-
mand for refrigeration”)
W
TV
Current temperature setpoint
Main menu > Settings > Refrigeration request > Temp request 0 V:
Main menu > Settings > Refrigeration request > Temp request 10 V:
Main menu > Settings > Refrigeration request > Temp request thresh:
Factory setting
Temp request at 0 V 35 °C
Temp request at 10 V 10 °C
Temp request threshold 25 °C