User Manual
2/4
Building Technologies Cable temperature sensor QAP1030/UFH CM1N1854en
Control Products and Systems 2017-05-22
Technical design
The QAP1030/UFH acquires the floor temperature via its NTC 3k sensing element. The
element’s resistance value changes depending on the temperature it acquires. It is
available for further handling by a suitable controller or room thermostat.
Mechanical design
The sensor consists of a 2-wire cable of approximately 4 m length with ferrules and an
NTC 3k sensing element.
Mounting notes
Mounting location: The sensor’s cable is to be run from the controller or room
thermostat to the sensing element’s location in the floor. It should preferably be run in a
protective plastic tube (from the controller or room thermostat to the measuring point in
the floor) – should it become necessary to replace the sensor at a later stage.
The sensing element must not get in contact with the electrical floor mat. The distance
of the measuring point in the floor from the wall should be a minimum of 60 cm.
Note:
To be able to acquire the floor temperature as accurately as possible, no furniture
should be placed on the floor where the sensing element is located.
Mounting example
1
8
5
4
Z
0
2