Data Sheet for Product
Table Of Contents
3/4
Smart Infrastructure Cable temperature sensor QAP1030/UFH CM1N1854en
2021-08-18
Disposal notes
The device is considered an electronics device for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic garbage.
Dispose of the device via the channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data
Measuring range -20...70 °C
1)
Sensing element NTC (3 k at 25 °C)
Time constant in static air 1.5 min
Measuring accuracy at 25 °C 0.3 K
Type of measurement and output Passive
Protection class II according to EN 60730-1
Connecting cable
Type
Length
End of cable
2-wire, interchangeable
H03VV-F2, 2 x 0.50 white
Approx. 4 m
Ferrules
Incl. packaging Approx. 0.165 kg
EU Declaration of Conformity A5W00034313-A
2)
1) If the connecting cable is not fixed, the lower temperature limit is only -5 °C!
2) The documents can be downloaded from http://siemens.com/bt/download.
Internal diagram
1840G01
NTC
Characteristics of NTC 3k sensing element at 25 °C
Temperature in °C -20 -15 -10 -5 0 5 10 15 20 25
Resistance in
29,751 22,257 16,815 12,825 9,867 7,656 5,991 4,722 3,750 3,000
Temperature in °C 30 35 40 45 50 55 60 65 70
Resistance in
2,416 1,958 1,597 1,310 1,081 897.0 747.9 627.0 528.0
Function data
Protection data
Electrical connection
Weight
Conformity