Siemens Cable temperature sensor QAP21.2 CE1N1833en
Building Technologies 2017-12-01
Disposal
The device is considered electrical and electronic equipment for disposal in terms of the
applicable European Directive and may not be disposed of as domestic garbage.
• Dispose of the device via the channels provided for this purpose.
• Comply with all local and currently applicable laws and regulations.
Technical data
Measurement range
max. (1-2 h/d)
−
30 ... + 180 °C
220 °C
Sensing element
LG
-Ni 1000
Time constant t
63
When fitted to the pipe
With protection pocket
<
20 s
<
30 s
Measurement accuracy at 0 °C
± 0.4 K (refer to "Function")
Measurement and output
P
assive
Protection degree of housing
IP67 acccording to EN 60529
Protection class
III
acccording to EN 60730-1
Mechanically
C
able tie or protection pocket
(supplied by thirds)
Electrical connections
Connecting cable
Cable length
Perm. cable length
2
-core, interchangeable, with ferrules
A
pprox. 1.5 m
R
efer to "Engineering notes"
EU conformity (CE)
A5W00040799 *)
Ambient temperature
Sensor sleeve
Connecting cable
−
30 ... + 180 °C (220 °C for max. 1-2 h/d)
− 50 ...
+
180 °C (220 °C for max. 1-2 h/d)
The product environmental declaration CE1E1701
*)
contains data on environmentally
compatible product design and assessments (RoHS compliance, materials composi-
tion, packaging, environmental benefit, disposal).
Sensor sleeve
Stainless steel V4A (1.4571)
Connecting cable
Silicon
Packaging (minigrip
bag)
PVC
Includi
ng packaging
0.056 kg
*) The documents can be downloaded from http://siemens.com/bt/download.
Functional data
Degree of protection
Connections
Environmental
conditions
Environmental
compatibility
Materials
Weight