User Manual

3/4
Siemens Cable temperature sensor QAP21.2 CE1N1833en
Building Technologies 2017-12-01
Disposal
The device is considered electrical and electronic equipment for disposal in terms of the
applicable European Directive and may not be disposed of as domestic garbage.
Dispose of the device via the channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data
Measurement range
max. (1-2 h/d)
30 ... + 180 °C
220 °C
Sensing element
LG
-Ni 1000
Time constant t
63
When fitted to the pipe
With protection pocket
<
20 s
<
30 s
Measurement accuracy at 0 °C
± 0.4 K (refer to "Function")
Measurement and output
P
assive
Protection degree of housing
IP67 acccording to EN 60529
Protection class
III
acccording to EN 60730-1
Mechanically
C
able tie or protection pocket
(supplied by thirds)
Electrical connections
Connecting cable
Cable length
Perm. cable length
2
-core, interchangeable, with ferrules
A
pprox. 1.5 m
R
efer to "Engineering notes"
EU conformity (CE)
A5W00040799 *)
Ambient temperature
Sensor sleeve
Connecting cable
30 ... + 180 °C (220 °C for max. 1-2 h/d)
50 ...
+
180 °C (220 °C for max. 1-2 h/d)
The product environmental declaration CE1E1701
*)
contains data on environmentally
compatible product design and assessments (RoHS compliance, materials composi-
tion, packaging, environmental benefit, disposal).
Sensor sleeve
Stainless steel V4A (1.4571)
Connecting cable
Silicon
Packaging (minigrip
bag)
PVC
Includi
ng packaging
0.056 kg
*) The documents can be downloaded from http://siemens.com/bt/download.
Functional data
Degree of protection
Connections
Environmental
conditions
Environmental
compatibility
Materials
Weight