Siemens Cable temperature sensor QAP21.2 CE1N1833en
Building Technologies 2017-12-01
Characteristic Accuracy
2500
−40 −20
0 20 40 60 80 100 120 140 160 180 200 220 240
500
2000
1500
1000
R
[Ω]
ϑ
1833D01
[°C]
−
50 0
50 100 150 200 250
2.0
1.5
1.0
0.5
0
−
0.5
−
1.0
−
1.5
−
2.0
∆ϑ
[K]
ϑ
1833D02
[°C]
R Resistance value in Ohm
ϑ Temperature in degrees Celsius
∆ϑ Temperature differential in Kelvin
Mechanical design
The cable temperature sensor consists of a sleeve (6 mm diameter, 50 mm long), sens-
ing element and connecting cable with ferrules.
The sensing element is accommodated in the sleeve which is flat on one side and to
which the connecting cable is attached.
The sensor is not suited for direct immersion in liquid media (without using a protection
pocket).
Accessories (not included with standard delivery)
Name
Type reference
Protection pocket, Ms63, PN10, immersion length 100 mm
ALT-SB100
1)
1) For other protection pocket accessories, refer to Data Sheet N1194.
Engineering notes
The permissible cable lengths are dependent on the type of controller used. For details,
refer to the Data Sheet of the relevant controller.
Mounting notes
The following mounting choices exist:
• Up to medium temperatures of 85 °C: with plastic cable tie (supplied by thirds)
• Up to medium temperatures of 220 °C: with stainless steel cable tie (supplied by
thirds)
≤ 85 °C
A
:
B:
≤ 220 °C
2
1833Z01
2
2
1
1
With the help of a protection pocket. The inside diameter of the pocket should match
the diameter of the sensor’s sleeve (e.g. 6.1 mm).
The sensor is supplied complete with Mounting Instructions.
Sensing element
Legend
On pipes
Indirect immersion