User Manual
3
Siemens
Datasheet
A6V11610632_en
--
_
a
Smart Infrastructure 2019-07-12
● For exhaust air temperature control: Always upstream of the exhaust air fan
● As a limit sensor for the supply air temperature: As close as possible to the air outlet into
the room
● For dew point control: Immediately after the spray trap of the air washer
Manually bend the probe so that it lies diagonally across the duct or in equally spaced
windings across the entire duct cross-section. The probe must not touch the duct wall.
Mounting instructions
Mounting instructions are enclosed in the package.
Mounting positions
Permitted Not permitted
Mounting examples
Disposal
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and regulations.