Data Sheet for Product
3
Siemens
Datasheet
A6V12251940_en--_b
Smart Infrastructure
2021-03-02
Type summary
Type reference
Immersion rod length
Sensing element
QAM1612.020
0.2 m
Pt 1000
QAM1630.020
0.2 m
NTC 10k
Ordering
When ordering, please give name and type reference, e.g.: Duct temperature sensor
QAM1612.020.
Equipment combinations
All systems or devices capable of acquiring and handling the sensor's passive output signal.
Notes
Mounting
Mounting location
● For supply air temperature control: Downstream from the fan if the fan is located after the
last air handling unit. Otherwise, after the last air handling unit with a minimum distance
of 0.5 m
● For extract air temperature control: Always upstream of the extract air fan
● As a limit sensor for the supply air temperature: As close as possible to the air outlet into
the room
● For dew point control: Immediately after the spray trap of the air washer
The immersion rod must not touch the duct wall.
The sensor is supplied complete with Mounting Instructions.
Mounting positions
Permitted
Not permitted
Mounting examples