Installation Instructions

Document No. 540-1031
Installation Instructions
October 26, 2016
Page 4 of 6 Siemens Industry, Inc.
NOTE:
When wiring any actuator that uses a 0 to
10V control signal and ties AC neutral to DC
common, an additional wire
must connect
the actuator AC neutral to the DC common
of the PTEC/TEC AO being used to control
the actuator.
24 Vac Modulating Control.
Actuator
Symbol
TEC
Connection
Function
Terminal
Connection
Standard
Color
1
H
Supply (SP)
G
Red
2
C
Neutral (SN)
G0
Black
8
AO3 15
(+)
0 to 10V
input signal
Y
Gray
--
C to AO3
16 (-)
Common
jumper
--
--
* AI 3 is switch selectable for voltage or current (on
controller board under cover).
Application 2843 -- VAV with 0-10V AO Heat
Modulation and CO2 Monitoring.