Installation Instructions
Document No. 540-1031
Installation Instructions
October 26, 2016
Page 2 of 6 Siemens Industry, Inc.
Warning/Caution Notation
WARNING
Personal injury/loss of life may
occur if you do not follow the
procedures as specified.
CAUTION
Equipment damage or loss of data
may occur if you do not follow the
procedures as specified.
Expected Installation Time
New controller installation
10 Minutes
Replacement (old controller has
removable terminal blocks)
6 Minutes
Replacement (old controller does not
have removable terminal blocks)
16 Minutes
NOTE:
You may require additional time for
database work at the field panel.
Required Tools and Materials
Small flat-blade screwdriver (1/8-inch blade
width)
Cabling and connectors
Cordless drill/driver set
Prerequisites
Wiring conforms to NEC and local codes and
regulations. For further information see the
Wiring Guidelines Manual
.
Room temperature sensor installed (optional).
24 Vac Class 2 power available.
Supply power to the unit is OFF.
Any application specific hardware or devices
installed.
NOTE:
If the controller is being installed on a box
with 1 or more stages of electric heat, the
550-809 MOV with pre-terminated spade
connectors must be installed across the
manufacturer-supplied airflow switch. MOVs
can be installed at the time the controller is
factory mounted; coordinate with the box
manufacturer prior to order placement. For
field installation, see
Metal Oxide Varistor Kit
Installation Instructions
(540-986).
Installation Instructions
NOTE:
All wiring must conform to national and local
codes and regulations (NEC, CE, etc.).
1. Secure the mounting rail in the controller’s
desired location.
2. Place the ESD wrist strap on your wrist and
attach it to a good earth ground.
3. Remove the controller from the static proof bag
and snap it into place on the mounting rail.
4. Connect the FLN.
5. Connect the point wiring (see
Wiring Diagram
s).
6. Plug the room temperature sensor cable into the
RTS port.
7. Connect the power trunk. DO NOT apply power
to the controller without first consulting the
specialist.