Data Sheet for Product

Technical Specification Sheet
Document No. 149-905
March 10, 2009
Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as
design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners.
© 2009 Siemens Building Technologies, Inc.
Siemens Building Technologies, Inc.
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
Your feedback is important to us. If you have
comments about this document, please send them to
sbt_technical.editor.us.sbt@siemens.com
Commissioning Sensor
Description
The Commissioning Sensor is a cost-effective
discharge air sensor used with controllers. It is
designed to be installed quickly into metal ductwork
and to connect to the controller's auxiliary sensor port
to provide a discharge air temperature point for use
with automated commissioning tools. The sensor's
resistance varies proportionally to the actual duct air
temperature being measured.
Applications
The controller uses the commissioning sensor when a
simple indication of duct temperature change is
needed. These sensors are also well-suited for
proofing HVAC equipment in heating and cooling
applications prior to the installation of room sensors.
.
Document No. 149-905
Country of Origin: US
Page 1 of 1
The commissioning sensor is not recommended for
closed-loop control or for applications where precise
temperature monitoring is required.
NOTE: An RJ-11 jack SHOULD NOT be added to
the 10K sensor leads for input into an RTS
port on a Siemens Terminal Equipment
Controller. The resulting sensor will not
work in this configuration, and is only
designed for use by an auxiliary input.
Specifications
Temperature Monitoring Range
10,000 ohms -40°F to 248°F (-40°C to 120°C)
100,000 ohms
39.2°F to 158°F (4°C to 70°C)
Output Signal Changing resistance
Calibration Point Information
Factory Calibration
Point
77°F (25°C)
Accuracy @ 77°F
± 5°F (± 3°C)
Thermistor
Resistance @
77°F (25°C)
100,000
10,000
(See NOTE)
Installation/
Calibration
Adjustment
None required
Cable Specs
Wire gauge 24 to 28 AWG
Plenum-rated Yes
Sensor Dimensional Specs
Probe Length
Insertion: 3.0 in. (76.2 mm)
Overall: 3.63 in. (92.2 mm)
Installation
cable length
8 feet (2.44 m) nominal
Ordering Information
QAM1030.008P50
Duct Temperature Sensor,
NTC 10K Type 2, 3" Probe
for Commissioning Only
QAM1035.008P50
Duct Temperature Sensor,
NTC 100K Type 2, 3" Probe
for Commissioning Only

Summary of content (1 pages)