Installation Instructions

Document No. 540-1029
Installation Instructions
October 26, 2016
Siemens Industry, Inc Page 3 of 4.
Wiring Diagram
The controller’s DOs control 24 Vac
loads only. The maximum rating is
12 VA for each DO. An external
interposing relay is required for any
of the following:
• VA requirements higher than the
maximum
• 110 or 220 Vac requirements
• DC power requirements
• Separate transformers used to
power the load.
(for example part number 540-147,
Terminal Equipment Controller
Relay Module)
Wiring for AI with a 4 to 20mA Sensor.
NOTE:
If the voltage/current switch is set to
current and a 4 to 20mA sensor is
connected to an AI, then special wiring
requirements must be followed.
NOTE:
When wiring any actuator that uses a 0 to
10V control signal and ties AC neutral to DC
common, an additional wire
must connect
the actuator AC neutral to the DC common
of the PTEC/TEC AO being used to control
the actuator.
24 Vac Modulating Control.
Actuator
Symbol
TEC
Connection
Function
Terminal
Connection
Standard
Color
1
H
Supply (SP)
G
Red
2
C
Neutral (SN)
G0
Black
8
AO3 15
(+)
0 to 10V
input signal
Y
Gray
--
C to AO3
16 (-)
Common
jumper
--
--