Data Sheet for Product

4/6
Smart Infrastructure Frost units QAF81... CA1N1284en
2021-08-31
Maintenance notes
The frost unit is maintenance-free.
Correct operation of the device can be checked by immersing the test loop in a vessel
of iced water.
Disposal notes
The devices are considered electronics devices for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic waste.
Dispose of the device via the channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data
Setpoint adjustment range W
h
5... 15 °C (23...59 °F)
Factory setting w 5 °C (41 °F)
Switching differential SD 2 1 °C (3.6 1.8 °F)
Repeatability 0.5 °C ( 0.9 °F)
Responsive length of sensor Approx. 0.3...1 m
Capillary length refer to "Type summary"
Type of switch Single pole change-over
Contact rating AC 250 V, 15(1.2) A
DC 30 V, 15(1.5) A
Reset mechanism QAF81.3, QAF81.6 Automatic
QAF81.6M Manual
External supply line protection (EU) Fuse slow max. 10 A
or
Circuit breaker max. 13 A
Characteristic B, C, D according to EN 60898
Admissible medium Air
Orientation Any
Electrical connection
Screw terminals for 1.5 mm
2
Cable entry Threaded M 20 x 1.5
Protection class I to EN 60 730-1
Protection degree of housing IP54 to EN 60 529
with cable gland (M20x1.5 IP65) IP65 to EN 60 529 (not included as standard)
Product standard EN 60730-1
EU Conformity (CE) CA1T1284xx*)
Environmental compatibility The product environmental declarations OE-T-99.41767d and
017_OE-T-99.41767e
*)
contain data on RoHS compliance,
materials composition, packaging, environmental benefit and
disposal
Ambient temperature
Max. operating temperature 70 °C (158 °F)
Min. operating temperature w + min. 2 °C (min. 3.6 °F)
Storage 30... 70 °C ( 22... 158 °F)
Destruction limit t
smax
140 °C (284 °F)
Materials
Housing Die-cast aluminium
Bellows housing Copper
Capillary Copper
Capillary contents Freon R134a
Contacts Ag (Silver)
Weight (including packaging) 0.9 kg
Maintenance None required
*) The documents can be downloaded from http://siemens.com/bt/download.