Data Sheet for Product

CA1N1284en
2021-08-31
Smart Infrastructure
1
284
Frost
U
nits
QAF81...
for air temperature monitoring
Robust aluminium die-cast housing
Responds to temperature change sensed over any 30 - 100 cm length of
capillary
Small switching differential
Good repeatability
Setpoint adjustment ( 5... 15 °C)
Protection standard IP54 (65)
Use
The frost unit QAF81... for air-side monitoring of the temperature of LTHW heating coils
in ventilation and air conditioning systems is used to prevent frost damage. It has a
small switching differential and good repeatability. The reset occurs automatically
(manual reset required with QAF81.6M).
The frost unit can be used to initiate the following frost protection functions:
Stop fan
Close outside air dampers
Open heating coil valve 100 %
Start heating coil pump
Switch off chiller (condenser) and humidifier
Trip visual and/or audible frost alarm
Typical applications
1284P01