Data Sheet for Product
CM1N1790en
201
7-12-01
Building Technologies
1
790
Immersion Temperature
Sensors
QAE26.9..
Use
Acquisition of flow or return temperature in heating, ventilating, and air conditioning
plants.
Type summary
Type Measuring
range
Cable
length
Material
connecting
cable
Time
constant
Mounting
length
Nominal
pressur
e
QAE26.9
−
40...+180 °C
1,2 m
silicone
<3 s
260 mm
PN 40
QAE26.90
−
50...+180 °C
2,0 m
silicone
<2,5 s
65 mm
PN 16
QAE26.91
−
50...+180 °C
2,0 m
silicone
<2,5 s
125 mm
PN 16
QAE26.93
−
50...+180 °C
2,0 m
silicone
<2.5 s
240 mm
PN 16
QAE26.95
−
50...+180 °C
2,0 m
silicone
<2.5 s
465 mm
PN 16
QAE1020.024
−
5...+105 °C
2,0 m
PVC
<2.5 s
240 mm
PN 16
Ordering
When ordering, please indicate give name and type reference, for exa mple:
Immersion temperature sensor QAE26.9.
Equipment combinations
All systems or devices capable of acquiring and handling the sensor’s passive
LG-Ni 1000 output signal.
1790P01