User Manual

Configurations
Push button configuration
4
A6V11610643_en--_a 11 | 16
NOTES:
1)
The master cannot change the Modbus address (register 764) to 246.
2)
The interval between every configuration command for register 764…768 from
Climatix
TM
is not more than 30 s. If it exceeds 30 s, the addressing mode ends
automatically.
3)
10-minute countdown starts from entering addressing mode.
4.5.2 Resetting Modbus parameters
Press the
push
button for
LED Action More details
1…5 s Constant red Press and hold the button
5…10 s LED off Press and hold the button
10…13 s
LED flashes
orange
Release the button
Release the button while LED still
flashes orange. LED keeps flashing
orange for 3 s, then turns red for 1s.
The reset to factory default 1) is
completed. LED turns to permanent
orange.
> 13 s
Returns to the
initial status
Release the button
Release after 13 s, resetting is
cancelled.
NOTE:
1)
Only Modbus address, baud rate and transmission format are reset to factory
default.
Reset Modbus parameters
to factory default settings