User Manual
Configurations
Push button configuration
4
10 | 16 A6V11610643_en--_a
4.5 Push button configuration
When DIP2-Position 7 is OFF (default setting), push button function is activated.
The following can be operated via push button:
● On-event addressing
● Resetting the Modbus parameters to factory default settings
4.5.1 On-event addressing (Climatix
TM
controllers configuration)
On-event addressing is a rapid configuration approach working together with
Siemens Climatix
TM
controllers.
The sensor is wired and connected to the Climatix
TM
controller via Modbus.
Press the
push
button for
LED Action More details
1…5 s Constant red Press and hold the button
5…10 s LED off Release the button
Entering the addressing mode, LED is
constant orange.
● Address is set to 246 temporarily.
● Baud rate is set to Auto and then
auto baud rate recognition is
done.
● Format is set to 1-8-E-1
temporarily.
Communication is established.
● Master writes the Modbus
parameters.
1)
● Master writes “1” into register
4x0768 ("Bus configuration.
command”) to activate the
change.
After a successful pairing, the LED
flashes green (1 s on / 5 s off).
Otherwise the LED turns back to its
original state.
● Time out after 30 s
2)
< 10 min
Constant orange
in addressing
mode
Press once and release the
button
If the LED is constant orange, a short
press of the push button stops and
exits the on-event addressing mode.
After exiting addressing mode, the
LED turns back to its original state.
Push button
Enter addressing mode
and configuration workflow
via push button