Installation Instructions

Installation Instructions
Document No. 129-460
December 12, 2017
Surface Mount Temperature Sensor
Item Number 129-460, Rev. EA Page 1 of 3
Product Description
The Surface Mount Temperature Sensor mounts
directly on a pipe inlet and senses the temperature
of water in the pipe.
Product Number
Product Number Output Signal
QAD2030U
10k NTC Type II
Thermistor
QAD2032U
10k NTC Type III
Thermistor
QAD2012U
1k Pt RTD (385α)
QAD2020U
1k @ 32°F Ni RTD
QAD2021U
1k @ 70°F Ni RTD
536-780 4 to 20 mA (30°F to 250°F)
544-089
1k Pt RTD (375α)
Contents
Description Quantity
Sensor 1
Mounting Kit:
Junction box
1
Strap
1
Wire nuts
2
No. 20 stretch tape
1 roll
NOTE: 536-780 also includes 4 to 20 mA
transmitter and two additional wire nuts.
Required Tools
Wire cutters
Knife
Duct tape
Wire brush, sandpaper or other abrasive tool
Medium flat-blade screwdriver
Expected Installation Time
13 minutes
Prerequisite
If the pipe is not insulated, a 12-inch to 18-inch
(30 cm to 46 cm) piece of insulation will be needed
to ensure an accurate temperature reading. The
insulation should be at least one-inch (25 mm) thick.
Installation
NOTE: To ensure accuracy, the sensor must be
mounted under insulation, away from drafts.
Do not cut any wire from the sensor.
1. If the pipe is insulated, remove a portion of the
insulation by making two cuts around the
circumference of the pipe (between 6 inches
and 12 inches [15 cm and 30 cm] apart).
2. Make a third cut perpendicular to the first two
cuts so that the insulation can be removed in
one piece. See Figure 1. Save this piece.
Figure 1. Cutting the Insulation.