Installation Instructions
Installation Instructions
Document No. 129-460
December 12, 2017
Surface Mount Temperature Sensor
Item Number 129-460, Rev. EA Page 1 of 3
Product Description
The Surface Mount Temperature Sensor mounts
directly on a pipe inlet and senses the temperature
of water in the pipe.
Product Number
Product Number Output Signal
QAD2030U
10k Ω NTC Type II
Thermistor
QAD2032U
10k Ω NTC Type III
Thermistor
QAD2012U
1k Ω Pt RTD (385α)
QAD2020U
1k Ω @ 32°F Ni RTD
QAD2021U
1k Ω @ 70°F Ni RTD
536-780 4 to 20 mA (30°F to 250°F)
544-089
1k Ω Pt RTD (375α)
Contents
Description Quantity
Sensor 1
Mounting Kit:
•
Junction box
1
•
Strap
1
•
Wire nuts
2
•
No. 20 stretch tape
1 roll
NOTE: 536-780 also includes 4 to 20 mA
transmitter and two additional wire nuts.
Required Tools
• Wire cutters
• Knife
• Duct tape
• Wire brush, sandpaper or other abrasive tool
• Medium flat-blade screwdriver
Expected Installation Time
13 minutes
Prerequisite
If the pipe is not insulated, a 12-inch to 18-inch
(30 cm to 46 cm) piece of insulation will be needed
to ensure an accurate temperature reading. The
insulation should be at least one-inch (25 mm) thick.
Installation
NOTE: To ensure accuracy, the sensor must be
mounted under insulation, away from drafts.
Do not cut any wire from the sensor.
1. If the pipe is insulated, remove a portion of the
insulation by making two cuts around the
circumference of the pipe (between 6 inches
and 12 inches [15 cm and 30 cm] apart).
2. Make a third cut perpendicular to the first two
cuts so that the insulation can be removed in
one piece. See Figure 1. Save this piece.
Figure 1. Cutting the Insulation.