Specifications
Monitoring range
55F to 95F (13C to 35C)
Sensing element
10K Negative Temperature Coefficient (NTC) Thermistor
Sensor Accuracy
±0.5F (0.3C), displayed to nearest whole degree at room sensor
Compatibility
Terminal Equipment Controller (TEC) using P1 protocol
Point Pickup Module
PXC Modular Series Controller with Expansion Module for P2 or BACnet ALN
PXC Compact Series Controller with FLN for P2 or BACnet ALN
Series 1000 Modular Equipment Controller (MEC) with FLNs and 32 MB or greater RAM for P2
ALN
Modular Building Controller (MBC) with PowerPC for P2 ALN
Frequency Range
16 channels of operation in the 2.4 GHz international license free ISM band (IEEE 802.15.4 radio
channels 11 through 26)
2405 to 2480 MHz 5 MHz channel spacing
Modulation
O-QPSK Direct Sequence Spread Spectrum radio in accordance with IEEE 802.15.4 specification
Agency Listings
UL 916
CSA (267AS-5630002)
Complies with FCC Part 15.247 (Regulations for Low Power Unlicensed Transmitters) FCC ID:
TKD-5630002
Range
Typical indoor range of 25 to 100 ft (8 to 30 m)
(Actual range varies based on environmental conditions)
Operating Temperature
32F to 122F (0C to 50C)
Operating Relative
Humidity
20% to 90% relative humidity (non-condensing)
Dimensions
L 4.50 × W 2.75 × D 1.21
(114 mm × 70 mm × 31 mm)
Power:
Battery
3.6 Volts Lithium AA (SAFT part number LS14500BA). These batteries are commonly
available at Batteries Plus and other battery distributors.
Battery Life
Typical 5-year life
(actual time varies based on operating environment, WRTS model, and settings)
Ordering Information
Description (White Housing, Battery Included)
Part Number
WRTS Sensing Only
QAA2290.EWSC
WRTS Sensing with Display*
QAA2290.DWSC
WRTS Sensing with Display*, Override, and Setpoint
QAA2290.FWSC
* Field selectable to display either Fahrenheit or Celsius units.