Data Sheet for Product

Disposal
The devices are considered electronics devices for disposal in terms of European Di-
rective 2012/19/EU and may not be disposed of as domestic waste.
Dispose of the device via the channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data
Operating voltage
refer to "Type summary"
Frequency
50/60 Hz at AC 24 V
Power consumption
QAA2061, QAA2061D
QAA2071
≤0.3VA
≤0.7W
External supply line protection
(EU)
Fuse slow max. 10 A
or
Circuit breaker max. 13 A
Characteristic B, C, D according to
EN 60898
or
Power source with current limitation of
max. 10 A
Perm. cable lengths
Copper cable 0.6 mm dia.
Copper cable 1 mm
2
Copper cable 1.5 mm
2
50 m
150 m
300 m
Measuring range
0...50 °C (R2 =
factory setting),
35...+ 35 °C (R1),
50...
+
50 °C (R3)
Sensing element
Pt 1000
Time constant
approx. 7 min
Measuring ac
curacy at AC 24 V / DC 24V in the
range of:
23 °C
25...+ 25 °C
50...
+
50 °C
±
0.50 K
±
0.75 K
± 0.9 K
Output signal, linear (terminal U1)
DC 0…10 V
0…50 °C or
35...+ 35 °C or 50...+ 50 °C
max.
±
1 mA
Output signal, linear (t
erminal I1)
Burden
4…20 mA
0…50 °C or
35...+ 35 °C or 50...+ 50 °C
refer to “Function”
Protection class
III according to EN 60730-1
Protection degree of housing
IP30 according to EN 60529
Connection terminals for
1
×
2.5 mm
2
or 2
×
1.5 mm
2
Operation
Climatic conditions
Temperature (housing with electronics)
Humidity
Mechanical conditions
IEC 60721
-3-3
class 3K5
15...+ 50 °C
0…95
% r. h. (non-condensing)
class 3M2
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
IEC 60721
-3-2
class 2K3
25...+ 70 °C
<
95 % r. h.
class 2M2
Power supply
Line lengths for
measuring signal
Functional data
Degree of protection
Electrical connections
Environmental conditions
4/6
Siemens Room temperature sensors QAA20..1.. CE1N1749en
Building Technologies 2014-07-30