User Manual
5/10
Siemens PXR11, PXR12 – System controllers CA1N9235en_03
Building Technologies 31 Jan 2009
LED Color Activity Meaning/Æ problem solution
Continuously off Everything OK.
LONWORKS® node configured
Continuously on Faulty LONWORKS® chip or service pin is being pressed.
SERVICE Red
Flashing LONWORKS® node not configured
Æ Configure with RXT10
TX Yellow Flashing Sending LONWORKS® data packets
RX Yellow Flashing Receiving LONWORKS® data packets
TX Yellow Flashing Transmitting data via COM2
RX Yellow Flashing Receiving data from COM2
Mounting
The PXR system controller can be snap-mounted on DIN rails or screwed directly to a
mounting plate.
Engineering
Engineering is carried out with the DESIGO TOOLSET (DTS):
• Create project with SYSTEM DESIGN (DTS-SD)
• Export completed project to DTS-PX
• Export completed project to RXT10
• Use the RXT10 to commission the RXC controllers (online)
• Use DTS-PX to commission PXR (online).
Optional:
• Modifications at field level (online)
• Reload modified RXT10 project into DTS-SD
• Export modified project to DTS-PX
• Re-commission the PXR using DTS-PX (online).
3
rd
Party Engineering:
• Importing of the 3
rd
party data is carried out with the PX OPEN MARLON Tool
Commissioning on the BACnet side (ALN)
The tool used for commissioning on the automation side (BACnet) is PX DESIGN, a
component of the DESIGO TOOLSET.
• An address is assigned to the device
• The PXR application downloaded.
Press the service pin on the PCB
or
Enter the BACnet neuron ID from the keyboard (NB: scope for error with this method!)
To check the procedure, a wink command can be sent to the relevant PXR controller.
L
ONWORKS®
COM2
A
ddressing