User Manual

5/10
Siemens PXR11, PXR12 – System controllers CA1N9235en_03
Building Technologies 31 Jan 2009
LED Color Activity Meaning/Æ problem solution
Continuously off Everything OK.
LONWORKS® node configured
Continuously on Faulty LONWORKS® chip or service pin is being pressed.
SERVICE Red
Flashing LONWORKS® node not configured
Æ Configure with RXT10
TX Yellow Flashing Sending LONWORKS® data packets
RX Yellow Flashing Receiving LONWORKS® data packets
TX Yellow Flashing Transmitting data via COM2
RX Yellow Flashing Receiving data from COM2
Mounting
The PXR system controller can be snap-mounted on DIN rails or screwed directly to a
mounting plate.
Engineering
Engineering is carried out with the DESIGO TOOLSET (DTS):
Create project with SYSTEM DESIGN (DTS-SD)
Export completed project to DTS-PX
Export completed project to RXT10
Use the RXT10 to commission the RXC controllers (online)
Use DTS-PX to commission PXR (online).
Optional:
Modifications at field level (online)
Reload modified RXT10 project into DTS-SD
Export modified project to DTS-PX
Re-commission the PXR using DTS-PX (online).
3
rd
Party Engineering:
Importing of the 3
rd
party data is carried out with the PX OPEN MARLON Tool
Commissioning on the BACnet side (ALN)
The tool used for commissioning on the automation side (BACnet) is PX DESIGN, a
component of the DESIGO TOOLSET.
An address is assigned to the device
The PXR application downloaded.
Press the service pin on the PCB
or
Enter the BACnet neuron ID from the keyboard (NB: scope for error with this method!)
To check the procedure, a wink command can be sent to the relevant PXR controller.
L
ONWORKS®
COM2
A
ddressing