Data Sheet for Product

5
Siemens A6V11664139_en--_i
Smart Infrastructure 2022-01-13
Disposal
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data
Power supply and HW information
Operating voltage
Safety Extra-Low Voltage SELV or
Protection by Extra Low Voltage per HD384
PoE: PoE switches and injectors must comply with IEEE
802.3at
AC 24 V ±20% (SELV / PELV)
AC 24 V class 2 (US)
DC 24 V ±15% (SELV / PELV)
DC 24 V class 2 (US)
DC 48 V (PoE Class 4, alternative A)
(PXM40-1, PXM50-1 only)
Frequency 50/60Hz
Maximum power consumption
At AC 24 V
At DC 24 V
PoE *)
PXM30.E
Max. 29 VA
Max. 17 W
- -
PXM40-1
Max. 32 VA
Max. 21 W
Max. 22 W *)
PXM50-1
Max. 42 VA
Max. 26 W
Max. 25 W *)
*) Applies to normal operation. Can be higher at start-up (IEEE 802.3at Class 4)
Processor Texas Instruments AM5727, 1.5 GHz, Dual Core
Memory 8 GB eMMC, 2 GB SDRAM (DDR3L)
Operating system Linux
Screw terminals for wire cross sections up to 2.5 mm
2
External supply line fusing (EU)
At AC / DC 24 V power
Non-renewable fuse max. 10 A slow or
circuit breaker max. 13 A
Tripping characteristic B, C, D per EN 60898 or
Power supply with current limitation of max. 10 A
Display
PXM30-1 PXM40-1 PXM50-1
Size 7.0“ 10.1  15.6 
Resolution 1024 x 600 1280 x 800 1366 x 768
Type TFT
Number of colors 16.2 mn
Viewing angle H/V typical 120 / 110° 150 / 145°
Backlit display LED, dimmable
Touch pad Projective capacitive
Life time at ambient temperature 20 °C (68 °F) 30,000 hours 50,000 hours 50,000 hours