Siemens A6V11664139_en--_i
Smart Infrastructure 2022-01-13
Disposal
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and regulations.
Technical data
Power supply and HW information
Operating voltage
Safety Extra-Low Voltage SELV or
Protection by Extra Low Voltage per HD384
PoE: PoE switches and injectors must comply with IEEE
802.3at
AC 24 V ±20% (SELV / PELV)
AC 24 V class 2 (US)
DC 24 V ±15% (SELV / PELV)
DC 24 V class 2 (US)
DC 48 V (PoE Class 4, alternative A)
(PXM40-1, PXM50-1 only)
Frequency 50/60Hz
Maximum power consumption
At AC 24 V
At DC 24 V
PoE *)
PXM30.E
Max. 29 VA
Max. 17 W
- -
PXM40-1
Max. 32 VA
Max. 21 W
Max. 22 W *)
PXM50-1
Max. 42 VA
Max. 26 W
Max. 25 W *)
*) Applies to normal operation. Can be higher at start-up (IEEE 802.3at Class 4)
Processor Texas Instruments AM5727, 1.5 GHz, Dual Core
Memory 8 GB eMMC, 2 GB SDRAM (DDR3L)
Operating system Linux
Screw terminals for wire cross sections up to 2.5 mm
2
External supply line fusing (EU)
At AC / DC 24 V power
Non-renewable fuse max. 10 A slow or
circuit breaker max. 13 A
Tripping characteristic B, C, D per EN 60898 or
Power supply with current limitation of max. 10 A
Display
PXM30-1 PXM40-1 PXM50-1
Size 7.0“ 10.1 15.6
Resolution 1024 x 600 1280 x 800 1366 x 768
Type TFT
Number of colors 16.2 mn
Viewing angle H/V typical 120 / 110° 150 / 145°
Backlit display LED, dimmable
Touch pad Projective capacitive
Life time at ambient temperature 20 °C (68 °F) 30,000 hours 50,000 hours 50,000 hours